Columbia Waste Oil Boilers


Model W60

  • HOT WATER OR STEAM
  • OPTIONAL TANKLESS COIL FOR POTABLE HOT WATER SUPPLY
  • LARGE REAR ACCESS FOR CLEANING
  • HEAVY GAUGE INCLINED WATER TUBE DESIGN
  • CHOICE OF 5 BURNER/NOZZLE COMBINATIONS TO MATCH YOUR REQUIREMENTS
  • 2-INCH REFRACTORY FLOOR WATER LEG DESIGN
Specifications and Data
Models W60 235/60 350/60 500/60 650*/60 800*/60 500 800*
Waste Oil GPH (approx.) 1.7 2.5 3.5 4.6 5.7 3.5 5.7
Input BTUH 235,000 350,000 500,000 650,000 800,000 500,000 800,000
Gross Output BTUH (approx.) 188,000 280,000 400,000 520,000 640,000 400,000 640,000
Gross H.P. 6 8 12 16 19 12 19
Combustion Volume, Cu. Ft. 9.9 9.9 10.5 10.5 10.5 10.5 10.5
Water Volume, Gals. 133 133 133 133 133 133 133
Boiler Width, without Controls 31.5" 31.5" 31.5" 31.5" 31.5" 31.5" 31.5"
Depth, with Burner and Smoke Hood 68" 68" 68" 68" 68" 68" 68"
Boiler Height 63.6" 63.6" 63.6" 63.6" 63.6" 63.6" 63.6"
Flue Outlet 10 10 10 10 10 10 10
Burner WO-B5 WO-B5 WO-B10 WO-B10 WO-B10 WO-B10 WO-B10
Boiler Weight (Dry) 1,700 lbs. 1,700 lbs. 1,730 lbs. 1,730 lbs. 1,730 lbs. 1,820 lbs. 1,850 lbs.
Total Shipping Weight (approx.) 2,450 lbs. 2,450 lbs. 2,475 lbs. 2,475 lbs. 2,475 lbs. 2,575 lbs. 2,575 lbs.
Potable Water Output @ 100� rise, gallons/hr. 228** 336** 470** 636** 750** 470 750
Compressed Air Requirements @ 40 psi 2 CFM 2 CFM 4 CFM 4 CFM 4 CFM 4 CFM 4 CFM
Electrical Requirements (all models) 115/60 15 Amp (220/50 7.5 Amp also available)
Water circulator not included
Fuels: Used crankcase oil, transmission and hydraulic fluids, synthetic oils, and other petroleum based lubricants (any weight combination up to SAE 50 including #1 and #2 fuel oil)
Agency Listings: (all models) ASME stamped, ETLM listed (per UL 796, UL 296A, NFPA 31, 70, and 211)
Standard Equipment: ASME Boiler, ASME Relief Valve, Waste Oil Burner w/Primary Control, J Pump and Filter Kit, Installation Kit & Manual, Insulated Flush Jacket, Theraltimeter Gauge, Operating and Manual High Limit Aquastats or Pressure Controls, Low Water Cut-Off
Canadian Boiler Registration: Nationally Registered by TSSA for sale and use in Canada
Operating Pressure: 15 psi Steam, 30 psi Water


Model LVW0 Model L24 Model W60 Model HRT20